Its interrupting capacity hits 220 kA at 240 V AC, 154 kA at 415 V, and 121 kA at 440 V — numbers that tell you this breaker is sized for high-fault panels where upstream coordination demands serious headroom.
Thermal derating and auxiliary hardware
The 50 A rating holds flat from 40 °C to 50 °C ambient, then derates to 48 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C.