Skip to main content
Siemens 3VA1150-6GD42-0AA0-ZD00 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-6GD42-0AA0-ZD00 Circuit Breaker, 50A, 70kA @

MPN3VA1150-6GD42-0AA0-ZD00

Siemens 3VA1 series, IEC frame 160, breaking capacity class H, Icu=70kA @ 415V, 4-pole, line protection TM210, FTFM, In=50A, overload protection Ir=50A fixed, short-circuit protection Ii=10 x In, N conductor protection 100%, nut keeper kit for DC Power OEM in China.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The Siemens 3VA1150-6GD42-0AA0-ZD00 is a 4-pole molded-case circuit breaker (MCCB) from the 3VA1 IEC frame 160 series, configured as a line-protection device with a fixed thermal-magnetic trip unit (TM210, FTFM). The continuous current rating is In = 50 A, with overload protection set fixed at Ir = 50 A and short-circuit protection fixed at Ii = 10 × In (500 A magnetic pickup). The N conductor is protected at 100% (full-rated neutral).

The 4-pole configuration with full neutral protection suits 3-phase + N systems common in commercial and light-industrial switchboards. The fixed thermal-magnetic trip means no field-adjustable overload dial — the Ir = 50 A is set at the factory, so verify the load current matches before specifying.

Frequently asked questions

How do I get current pricing and availability for 3VA1150-6GD42-0AA0-ZD00?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of your quote request.

What is the breaking capacity and rating of this MCCB?

It has a breaking capacity Icu = 70 kA at 415 V AC (Class H), a continuous rating In = 50 A, fixed overload protection Ir = 50 A, and fixed short-circuit protection Ii = 10 × In (500 A).

MPN
3VA1150-6GD42-0AA0-ZD00