Skip to main content
Siemens 3VA1150-6MH32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1150-6MH32-0AA0 MCCB, 50 A, 220 kA at 240 V

MPN3VA1150-6MH32-0AA0
Active

Siemens SENTRON 3VA1150-6MH32-0AA0, molded case circuit breaker, starter protection, 3-pole, 50 A, TM120M release, 220 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1150-6MH32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection

Ratings

3VA1150-6MH32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.14.6 W

Protection & Trip Unit

3VA1150-6MH32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
Overcurrent protection functionI
Ground-fault monitoringWithout

Construction & Connection

3VA1150-6MH32-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1150-6MH32-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1150-6MH32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1150-6MH32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this 3VA1150-6MH32-0AA0 is and what it does

Siemens SENTRON molded case circuit breaker, starter protection, 3-pole, 50 A at 45 °C, TM120M release, adjustable magnetic trip 350 A to 800 A. Breaking capacity is the headline here: 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — that puts it in the high-interrupting class for industrial distribution where fault currents can hit 150 kA near a transformer secondary. At 500 V and 690 V it holds 7.5 kA, which is still adequate for most motor starters on those voltage levels.

Mounting and panel fit — dimensions and IP rating

The 3VA1150-6MH32-0AA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard 3-pole MCCB footprint that drops into most DIN-rail or screw-mounted panel layouts without re-drilling. IP40 on the front means it's protected against tools and wires >1 mm, but not against water ingress; keep it inside a sealed enclosure in washdown areas.

Thermal derating and operating limits

Continuous current holds 50 A up to 50 °C ambient, then derates to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. If your panel runs hot — say, near a drive bank — size the load or the breaker accordingly. Operating range is -25 °C to 70 °C; storage from -40 °C to 80 °C.

MPN
3VA1150-6MH32-0AA0