Skip to main content
Siemens 3VA1163-1AA32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA32-0DA0 Switch Disconnector, 63 A, UVR

MPN3VA1163-1AA32-0DA0

Siemens SENTRON 3VA1 switch disconnector, IEC frame 160, 3-pole, SD100, In=63 A, without overload or short-circuit protection, undervoltage release 208-230 V AC 50/60 Hz, busbar connection, front terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-1AA32-0DA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1163-1AA32-0DA0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1163-1AA32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-1AA32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1163-1AA32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-1AA32-0DA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this part actually is

The Siemens 3VA1163-1AA32-0DA0 is a switch disconnector in an MCCB-style housing from the SENTRON 3VA1 family. It carries a 63 A rated continuous current (Iu) across three poles, with a rated insulation voltage of 800 V and a max AC operational voltage of 690 V at 50/60 Hz. The front-terminal busbar connection suits it for panel-mounted isolation duty where you need a visible disconnect without overcurrent protection built in.

What the undervoltage release means for your circuit

That's standard for applications where you need the load to stay off after a brownout or power loss: conveyors, pumps, or any motor circuit where an automatic restart could be a safety or process risk. The UVR has no leading contact, so it doesn't provide early warning ahead of the dropout.

The 3VA1163-1AA32-0DA0 shares the same 70 mm depth, 76.2 mm width, and 130 mm height as the rest of the 3VA1 160 A frame family. The front terminal accepts busbar connection for the main circuit — no lug terminals here, so plan for a busbar system rather than ring-tongue or fork crimps. An optional motor drive can be added externally if remote operation is needed.

The lifecycle stage is listed as current, meaning Siemens still produces this order code as an active catalog item. No successor has been announced.

Frequently asked questions

Where can I buy 3VA1163-1AA32-0DA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will 3VA1163-1AA32-0DA0 drop into a panel specified around 3VA1112-5EF32-0CA0 without rewiring?

The 3VA1163-1AA32-0DA0 shares the same 70 mm depth, 76.2 mm width, and 130 mm height as the 3VA1112-5EF32-0CA0, so the physical footprint and DIN-rail mounting are identical. However, the 3VA1163 uses busbar connection on the front terminal, while the 3VA1112 uses lug terminals — you may need to adapt the busbar arrangement or add busbar adapters. The UVR wiring is the same 208-230 V AC control circuit.

What compliance documentation does Siemens provide for this part?

As a SENTRON 3VA1 series component, this switch disconnector carries the manufacturer's standard declarations — CE marking for the European market, and the design follows IEC/EN 60947-3 for switch-disconnector performance. Specific RoHS and REACH compliance documentation is available from Siemens on request.

MPN
3VA1163-1AA32-0DA0