Siemens 3VA1163-1AA32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA32-0HA0 SENTRON Switch Disconnector, 63 A

MPN3VA1163-1AA32-0HA0

Siemens SENTRON 3VA1 IEC frame 160, 3-pole switch disconnector SD100, In=63 A, without overload or short-circuit protection, shunt trip (STL) 12-30 V DC / 24 V AC 50/60 Hz, busbar connection, front terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-1AA32-0HA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1163-1AA32-0HA0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1163-1AA32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-1AA32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1163-1AA32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-1AA32-0HA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1163-1AA32-0HA0 is a SENTRON 3VA1 switch disconnector in an MCCB-style housing, rated for 63 A continuous current (Iu) at up to 690 V AC 50/60 Hz or 500 V DC. It is a pure disconnect — no overload or short-circuit protection — so it serves as a manual load-break switch or isolation point in a distribution panel, not as a circuit breaker. The built-in shunt trip (STL) release, rated 12–30 V DC / 24 V AC, lets a remote signal or safety circuit open the switch under load, which is useful for emergency-stop chains or controlled shutdown sequences.

The 63 A continuous rating at 690 V AC covers most 400 V three-phase motor and distribution loads up to roughly 44 kW, but the part carries no trip curve — it will not clear an overload or fault. That makes it a line-side disconnect or maintenance isolator, not a branch-circuit protector. The 500 V DC rating is useful for DC bus or battery-string isolation, but verify the DC switching capacity for your specific load type; the evidence does not list a DC breaking capacity figure. The front terminals accept busbar connection (not lug or box terminals), so the panel layout must use a busbar system rather than individual cable lugs. The 70 mm depth, 76.2 mm width, and 130 mm height match the standard 3VA1 frame-160 footprint, meaning it occupies the same DIN-rail space as a 3-pole MCCB of the same frame size.

Panel integration

Front terminals accept busbar connection, so plan the busbar routing before wiring.

Frequently asked questions

Will 3VA1163-1AA32-0HA0 fit in a panel designed for 3VA1110-5EE32-0JA0?

Yes, both parts share the same 70 mm depth, 76.2 mm width, and 130 mm height, and both use front terminals with busbar connection. The switch disconnector drops into the same DIN-rail footprint without rewiring the busbar system.

MPN