Skip to main content
Siemens 3VA1163-1AA32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA32-0HC0 Switch Disconnector, 63 A, 3-Pole

MPN3VA1163-1AA32-0HC0

Siemens SENTRON 3VA1 IEC frame 160 switch disconnector, 3-pole SD100, In=63A, without overload or short-circuit protection, shunt trip (STL) 12-30V DC / 24 V AC, 2 auxiliary switches HQ, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-1AA32-0HC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1163-1AA32-0HC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1163-1AA32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-1AA32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1163-1AA32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-1AA32-0HC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1163-1AA32-0HC0 is a SENTRON 3VA1 switch disconnector in MCCB-style construction, but it carries no overload or short-circuit protection — it is a disconnecting means only, rated for 63 A continuous current (Iu) on a 160 A frame. That means this part functions as a manual load-break switch for isolation and safety disconnection, not as a circuit breaker. It is designed for applications where upstream protection already exists and the panel needs a lockable, rated disconnect with auxiliary signaling. Rated for 690 V AC 50/60 Hz and 500 V DC, with a short-time withstand of 2 kA for 1 second — enough for fault clearing coordination with upstream devices in most industrial distribution panels.

Built-in shunt trip and auxiliary contacts

Factory-fitted with a shunt trip (STL) release rated 12–30 V DC / 24 V AC 50/60 Hz, allowing remote tripping from a PLC or emergency-stop circuit. Two HQ auxiliary switches (form C) provide status feedback — useful for SCADA or panel indication. No undervoltage release is present, and no communication module is built in. If you need UVR or fieldbus, that requires a different variant or an add-on kit.

Measures 70 mm deep, 76.2 mm wide, 130 mm tall — the standard 3VA1 3-pole footprint. Front terminals accept busbar connection; IP40 on the front face keeps out tools and dust but not water jets. Maximum power dissipation 38 W at rated current — account for that in enclosure thermal calculations.

Frequently asked questions

Will 3VA1163-1AA32-0HC0 drop into a panel designed for 3VA1110-5EE32-0JA0 without rewiring?

Both share the same 70 mm depth, 76.2 mm width, and 130 mm height, and both use front terminals. However, 3VA1110-5EE32-0JA0 is a molded case circuit breaker with lug terminals and overcurrent protection, while this part is a switch disconnector with busbar connection — the functional role and wiring method differ, so verify the panel's protection scheme before substituting.

MPN
3VA1163-1AA32-0HC0