Siemens 3VA1163-1AA32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA32-0JC0 SENTRON Switch Disconnector, 63 A

MPN3VA1163-1AA32-0JC0

Siemens SENTRON 3VA1 IEC frame 160, switch disconnector SD100, 3-pole, 63 A, shunt trip STL 110-127 V DC/AC, 2 HQ auxiliary switches, busbar connection, front terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-1AA32-0JC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1163-1AA32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Power loss, max.38 W
3VA1163-1AA32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-1AA32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1163-1AA32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-1AA32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1163-1AA32-0JC0 is a 3-pole switch disconnector in the 3VA1 IEC frame 160, rated at 63 A with no overload or short-circuit protection — it is a pure disconnecting means, not a circuit breaker.

63 A flat derating to 70 °C

That simplifies panel sizing in warm enclosures or near heat-generating gear. Maximum power loss is 38 W at rated load, so the thermal budget for the enclosure is modest.

Shunt trip and auxiliary switch complement

The integrated shunt trip (STL) accepts 110-127 V DC or AC 50/60 Hz, letting you trip the disconnector remotely from a PLC or E-stop circuit. Two HQ auxiliary switches (form C) provide position feedback — one for open/closed status, the second for a separate signal path. No undervoltage release is fitted, and no voltage trigger is present; the only remote-trip path is the shunt coil.

Mounting and connection

Footprint is 70 mm deep by 76.2 mm wide by 130 mm tall — a standard 3-pole MCCB-style envelope that fits most DIN-rail or panel-mount cutouts. Main circuit connection is via busbar with front terminals, so it accepts common busbar systems without adapters. An optional motor drive is listed as a field-installable extension.

MPN