Skip to main content
Siemens 3VA1163-1AA32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA32-0JH0 SENTRON Switch Disconnector, 63 A

MPN3VA1163-1AA32-0JH0

Siemens SENTRON 3VA1 IEC frame 160, switch disconnector, 3-pole, In=63 A, shunt trip (STL) 110-127 V DC/AC, 2 auxiliary switches HQ + 1 trip alarm switch HQ, busbar front terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-1AA32-0JH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1163-1AA32-0JH0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1163-1AA32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-1AA32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1163-1AA32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-1AA32-0JH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1163-1AA32-0JH0 is a SENTRON 3VA1 switch disconnector in MCCB design, rated for 63 A continuous current (Iu) across three poles. It provides no overload or short-circuit protection — its job is safe isolation under load, not circuit protection.

The 63 A rated continuous current (Iu) sets the maximum load it can carry continuously without exceeding temperature limits. This is a switch disconnector, not a breaker — it is sized for isolation duty, so the 63 A figure governs the conductor and busbar sizing upstream. The 3-pole design handles three-phase circuits up to 690 V AC or 500 V DC (max rated operational voltage).

Integration notes

The 3VA1163-1AA32-0JH0 mounts with a busbar connection on the main circuit and front terminals for wiring access. Dimensions are 70 mm deep, 76.2 mm wide, and 130 mm tall — fitting the standard 3VA1 frame-160 footprint. The shunt trip release (STL) is wired separately from the main load circuit; verify control voltage matches the 110–127 V DC/AC rating before energizing. The auxiliary contact block provides 2 CO contacts plus 1 trip alarm CO contact, all HQ-rated for signal feedback to a PLC or status lamp.

Frequently asked questions

Where can I buy 3VA1163-1AA32-0JH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the difference between 3VA1163-1AA32-0JH0 and 3VA1110-5EE32-0JA0?

The 3VA1110-5EE32-0JA0 is a molded case circuit breaker (line protection) with overcurrent release, rated 100 A, while the 3VA1163-1AA32-0JH0 is a switch disconnector with no overcurrent protection, rated 63 A. They share the same frame-160 footprint and dimensions, so the switch disconnector can mount in the same panel cutout, but the breaker includes overload and short-circuit protection that the disconnector lacks.

Does 3VA1163-1AA32-0JH0 include a shunt trip?

Yes, it includes a shunt trip (STL) release rated for 110–127 V DC/AC.

MPN