Skip to main content
Siemens 3VA1163-1AA32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA32-0KC0 SENTRON Switch Disconnector, 63 A

MPN3VA1163-1AA32-0KC0

Siemens SENTRON 3VA1 IEC frame 160, 3-pole SD100 switch disconnector, 63 A, without overload or short-circuit protection, shunt trip (STL) 220-250 V DC; 208-277 V AC, 2 auxiliary switches HQ, busbar connection, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-1AA32-0KC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1163-1AA32-0KC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1163-1AA32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-1AA32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1163-1AA32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-1AA32-0KC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1163-1AA32-0KC0 is a 3-pole switch disconnector in the 3VA1 IEC frame 160 platform, rated for 63 A continuous current (Iu) without integral overload or short-circuit protection — it's a pure isolating and switching device, not a circuit breaker.

Rated insulation voltage Ui is 800 V, and maximum operational voltage reaches 690 V AC (50/60 Hz) or 500 V DC — so it's comfortable in 400 V or 480 V distribution panels and in DC bus circuits up to 500 V. The limited short-time withstand is 2 kA at both 1 s and 0.5 s intervals, which means this disconnector is intended for downstream isolation behind a higher-rated upstream protective device; it's not rated to break fault current on its own.

The main current circuit connects via busbar connection with front terminals.

Frequently asked questions

What is the closest functional second-source to 3VA1163-1AA32-0KC0?

The 3VA1110-5EE32-0JA0 is a 100 A molded-case circuit breaker in the same 3VA1 frame 160 with identical footprint and busbar connection, but it includes thermal-magnetic overcurrent protection (TM220) and higher interrupting ratings. It lacks the factory shunt trip and auxiliary switches that this disconnector carries. It will drop into the same panel without rewiring the bus, but it is not a direct functional replacement — this part is a pure switch disconnector, not a breaker.

MPN
3VA1163-1AA32-0KC0