Siemens 3VA1163-1AA36-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA36-0AE0 SENTRON Switch Disconnector, 63 A

MPN3VA1163-1AA36-0AE0

Siemens SENTRON 3VA1 IEC frame 160, switch disconnector, 3-pole, In=63 A, without overload or short-circuit protection, clamp connection, 4 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-1AA36-0AE0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1163-1AA36-0AE0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1163-1AA36-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-1AA36-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA1163-1AA36-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-1AA36-0AE0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Switch disconnector for isolation duty

The Siemens SENTRON 3VA1163-1AA36-0AE0 is a 3-pole switch disconnector in the MCCB-style 3VA1 frame, rated for 63 A continuous current (Iu) at up to 690 V AC 50/60 Hz or 500 V DC. It provides no overload or short-circuit protection — this is a pure isolating switch for load-break and visible disconnect applications, not a circuit breaker.

The 63 A rated continuous current (Iu) is the maximum uninterrupted load this switch can carry in free air at 40 °C ambient — sized for a 30–50 A motor feeder or a 63 A resistive load branch where isolation, not overcurrent protection, is the function. The short-time withstand rating of 2 kA at 1 s (and at 0.5 s) tells you the switch can survive a fault current of that magnitude for that duration while closed; upstream protection must clear before the limit is exceeded. The 15 000 mechanical endurance cycles are typical for a panel-main disconnect, not a daily-operating contactor.

Mounts in the standard 3VA1 frame footprint: 70 mm deep, 76.2 mm wide, 130 mm tall — same cutout and drilling pattern as the 3VA1 MCCB line, so it drops into an existing panel layout without rework. The 4 HQ auxiliary switches (4 CO) are factory-fitted and wired to the front terminal block; no separate order for aux contacts. The undervoltage release is not present (no UVR), and no communication module is installed — this is a standalone disconnect. A motor drive can be added as an optional extension (field-fit).

Frequently asked questions

What is the difference between this switch disconnector and the 3VA1110-5EF36-0AD0 MCCB?

The 3VA1110-5EF36-0AD0 is a molded-case circuit breaker with a TM240 thermal-magnetic trip unit (100 A frame, LI protection), while the 3VA1163-1AA36-0AE0 is a switch disconnector with no overcurrent protection — it provides load-break isolation only. Both share the same 3VA1 frame dimensions (70 mm deep, 76.2 mm wide, 130 mm tall) and front-terminal connection, so a panel cutout designed for the MCCB will accept the switch disconnector without modification.

Where can I buy 3VA1163-1AA36-0AE0?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest commercial terms.

What auxiliary contacts does this switch ship with?

It ships with 4 factory-fitted HQ auxiliary switches, providing 4 CO (changeover) contacts wired to the front terminal block.

MPN