Siemens 3VA1163-1AA36-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA36-0CH0 Switch Disconnector, 63 A, 3-Pole

MPN3VA1163-1AA36-0CH0

Siemens SENTRON 3VA1 switch disconnector, IEC frame 160, 3-pole SD100, In=63 A, without overload or short-circuit protection, clamp connection, undervoltage release 120-127 V AC 50/60 Hz, 2 auxiliary switches HQ + 1 trip alarm switch HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-1AA36-0CH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1163-1AA36-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Power loss, max.38 W

Construction & Connection

3VA1163-1AA36-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-1AA36-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1163-1AA36-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-1AA36-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1163-1AA36-0CH0 is a 3-pole switch disconnector in MCCB design, rated at 63 A continuously from 40 °C through 70 °C ambient — no derating needed across that span. It is built on the IEC frame 160 platform and ships without overload or short-circuit protection elements, so it functions purely as a load-break disconnect for isolation and switching duty. Rated operating voltage is 690 V AC and 500 V DC, with an insulation voltage of 800 V. The front face carries IP40 protection — suitable for enclosed panel mounting where the front is behind a door.

Undervoltage Release and Auxiliary Switching

This unit comes fitted with an undervoltage release (UVR) coil rated for 120–127 V AC 50/60 Hz. When control voltage drops below the dropout threshold, the UVR trips the disconnect open — standard for preventing automatic restart after a power loss on machinery where that would be a safety hazard. The auxiliary switch configuration includes 2 HQ auxiliary switches plus 1 HQ trip alarm switch, giving three CO contacts total for status feedback to a PLC or indication panel.

Mechanical Life and Power Loss

Typical mechanical service life is 15,000 operating cycles — adequate for isolation duty where the disconnect is operated a few times per shift, not for high-frequency motor starting. Maximum power loss is 38 W at rated current, which factors into enclosure thermal calculations if multiple units are ganged in a small cabinet.

Lifecycle and Sourcing

Storage temperature range is -40 °C to 80 °C; operating ambient is -25 °C to 70 °C. The mechanical service life is 15,000 cycles typical.

Frequently asked questions

What is the rated current of 3VA1163-1AA36-0CH0?

The rated current is 63 A continuous, with no derating required from 40 °C through 70 °C ambient.

Where can I buy 3VA1163-1AA36-0CH0?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing.

MPN
3VA1163-1AA36-0CH0