Skip to main content
Siemens 3VA1163-1AA36-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA36-0DC0 SENTRON Switch Disconnector, 63 A

MPN3VA1163-1AA36-0DC0

Siemens SENTRON 3VA1 IEC frame 160, switch disconnector 3VA1163-1AA36-0DC0, 3-pole, 63 A, without overload or short-circuit protection, undervoltage release 208-230 V AC, 2 auxiliary switches HQ, front terminal connection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-1AA36-0DC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1163-1AA36-0DC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W

Construction & Connection

3VA1163-1AA36-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-1AA36-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-1AA36-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-1AA36-0DC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What it is and what it is not

The Siemens 3VA1163-1AA36-0DC0 is a SENTRON switch disconnector in the 3VA1 IEC frame 160 family, rated at 63 A continuous current (Iu) across 3 poles. It is explicitly a switch disconnector — not a molded case circuit breaker — meaning it provides no overload or short-circuit protection. The product designation and description confirm it is built for isolation and switching duty only, with a latching endurance of 15 000 operations. The unit carries an undervoltage release (UVR) rated 208-230 V AC 50/60 Hz, with a leading contact option not present (No). Two HQ auxiliary switches (changeover contacts) are integrated, providing status feedback for the disconnector position. The UVR ensures the switch opens automatically if control voltage drops below the dropout threshold — a standard requirement for safety disconnects in motor feeder circuits.

Key ratings and what they mean for fit

Rated continuous current Iu = 63 A means this disconnector is sized for a 63 A feeder or motor branch circuit — it must be paired with upstream overcurrent protection (fuse or MCCB) since the device itself has none. The rated insulation voltage Ui = 800 V and maximum operational voltage Ue = 690 V AC / 500 V DC define the system voltage limits; at 690 V AC the part can safely isolate the load. The 38 W maximum power loss at rated current matters for enclosure thermal management — in a sealed panel with multiple devices, that heat must be factored into the cooling calculation. The short-time withstand ratings (Limited To 1 S = 2 kA, Limited To 0.5 S = 2 kA) indicate the disconnector can carry a fault current of 2 kA for up to 1 second without damage — adequate for coordination with upstream protective devices that clear faster. IP40 on the front means protection against tools and small wires (≥1 mm) but not water; install in a panel with IP54 or better enclosure if washdown is present.

Dimensions and panel integration

The 3VA1163-1AA36-0DC0 measures 130 mm height × 76.2 mm width × 70 mm depth. Front terminal connection for the main circuit uses clamp-type terminals; the 3-pole footprint matches the standard 3VA1 frame 160 cutout. The auxiliary switches and UVR are factory-installed — no field-assembly of these accessories required, which simplifies BOM line items and panel wiring. An optional motor drive can be added (product extension / optional / motor drive = Yes) for remote switching.

Frequently asked questions

What is the difference between 3VA1163-1AA36-0DC0 and 3VA1110-5EE32-0DC0?

The 3VA1163-1AA36-0DC0 is a switch disconnector with no overload or short-circuit protection, while the 3VA1110-5EE32-0DC0 is a molded case circuit breaker with a TM220 thermal-magnetic release rated 100 A. Both share the same frame, dimensions, auxiliary switch count, and undervoltage release. Choose the disconnector for isolation-only duty; choose the MCCB when integrated protection is required.

Will 3VA1163-1AA36-0DC0 fit in a panel designed for 3VA1110-5EE32-0DC0?

Yes, the dimensions are identical: 130 mm height × 76.2 mm width × 70 mm depth, same front terminal arrangement. The cutout and mounting pattern are the same within the 3VA1 frame 160 family. No rewiring or panel modification is needed for the physical swap.

MPN