Skip to main content
Siemens 3VA1163-1AA36-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA36-0KA0 SENTRON Switch Disconnector, 63A

MPN3VA1163-1AA36-0KA0

Siemens SENTRON 3VA1 IEC frame 160, switch disconnector in MCCB design, 3-pole, 63 A, shunt trip (STL) 220-250 V DC / 208-277 V AC, front terminal connection, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-1AA36-0KA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1163-1AA36-0KA0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1163-1AA36-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-1AA36-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1163-1AA36-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-1AA36-0KA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1163-1AA36-0KA0 is a SENTRON 3VA1 switch disconnector in an MCCB (molded case circuit breaker) mechanical design — same frame, same DIN-rail footprint, but built purely for isolation and switching, not overcurrent protection. Rated continuous current Iu is 63 A, with no overload or short-circuit protection onboard. That makes it the right choice for a manual disconnect point where upstream protection already exists, or for safe isolation during maintenance on a 3-pole load circuit. The integrated shunt trip release (STL) operates on 220–250 V DC or 208–277 V AC, letting you trip the disconnector remotely via a control signal — useful for emergency-stop chains or remote load shedding where you need to break the circuit without walking to the panel. No undervoltage release is fitted, so the disconnector holds in regardless of control voltage loss; only a deliberate shunt-trip pulse opens it.

Three-pole, 70 mm deep, 76.2 mm wide, 130 mm tall — the same compact 3VA1 frame dimensions as the equivalent breaker versions. Front terminal connection for the main circuit, clamp-type terminals. The 3VA1 frame accepts an optional motor drive, so this disconnector can be automated for remote switching without losing the manual disconnect function. No auxiliary contacts are fitted as standard; if you need status feedback, plan for an add-on auxiliary contact block.

Voltage and endurance

Mechanical endurance is 15,000 operating cycles. Power loss at rated current maxes at 38 W.

Frequently asked questions

How do I get pricing and availability for 3VA1163-1AA36-0KA0?

Submit an RFQ through the storefront. This part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

What is the closest functional second-source to 3VA1163-1AA36-0KA0?

The 3VA1110-5EE32-0JA0 is a line-protection MCCB (not a switch disconnector) with the same 3-pole, 70x76.2x130 mm frame and shunt trip option, but it carries a 100 A rating with a TM220 thermal-magnetic release and full overcurrent protection. It will physically drop into the same panel cutout and bus connection, but it is a circuit breaker, not a switch disconnector — it adds protection and removes the pure-isolation role. If you need a switch disconnector, the 3VA1163-1AA36-0KA0 is the correct part.

What is the depth of 3VA1163-1AA36-0KA0?

70 mm.

What is the width of 3VA1163-1AA36-0KA0?

76.2 mm.

Will 3VA1163-1AA36-0KA0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?

Yes. Both parts share the same 3VA1 frame dimensions (70 mm deep, 76.2 mm wide, 130 mm tall) and front-terminal connection arrangement, so the physical footprint and bus-bar positions are identical. No rewiring of the main circuit is needed for the swap, but the 3VA1163-1AA36-0KA0 is a switch disconnector without overcurrent protection, so the upstream protection must already cover the load.

MPN