Siemens 3VA1163-1AA42-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA42-0HC0 SENTRON Switch Disconnector, 63 A

MPN3VA1163-1AA42-0HC0

Siemens SENTRON 3VA1163-1AA42-0HC0, switch disconnector in MCCB design, IEC frame 160, 4-pole SD100, 63 A, without overload or short-circuit protection, shunt trip (STL) 12-30V DC / 24 V AC, 2 auxiliary switches HQ, busbar connection, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-1AA42-0HC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1163-1AA42-0HC0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Power loss, max.38 W

Construction & Connection

3VA1163-1AA42-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-1AA42-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-1AA42-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-1AA42-0HC0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

Switch disconnector without overload or short-circuit protection

The Siemens 3VA1163-1AA42-0HC0 is a 4-pole SENTRON switch disconnector in MCCB-style housing, rated 63 A continuous with no overload or short-circuit protection elements — it is a disconnect-only device for isolation and switching duty. The 63 A rating holds across the full ambient range from 40 °C to 70 °C (no derating needed up to the maximum operating temperature), so it fits warm enclosures without a current penalty. It carries a built-in shunt trip (STL) release rated 12-30 V DC / 24 V AC 50/60 Hz, plus two HQ auxiliary switches (form C, CO contacts). The shunt trip allows remote or emergency trip initiation via a control signal; the auxiliary switches report the main contact position back to the PLC or status panel. No undervoltage release is fitted, and no communication module is integrated.

DIN-rail mounting and wiring

Dimensions are 70 mm deep, 101.6 mm wide, 130 mm tall. Front terminals accept busbar connection for the main circuit. Mechanical service life is 15,000 switching cycles typical. Power loss at rated current is 38 W maximum.

Frequently asked questions

Will 3VA1163-1AA42-0HC0 drop into a panel specified for 3VA1110-5EF36-0AD0?

No — the 3VA1110-5EF36-0AD0 is a 3-pole, 76.2 mm wide MCCB with overcurrent protection, while this 4-pole disconnector is 101.6 mm wide and has no trip unit. The panel cutout, wiring, and protection scheme are different.