Skip to main content
Siemens 3VA1163-1AA42-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-1AA42-0JA0 SENTRON Switch Disconnector, 63 A

MPN3VA1163-1AA42-0JA0

Siemens SENTRON 3VA1163-1AA42-0JA0, switch disconnector, IEC frame 160, 4-pole SD100, In=63 A, without overload or short-circuit protection, shunt trip release 110-127 V DC/AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-1AA42-0JA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1163-1AA42-0JA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Power loss, max.38 W

Construction & Connection

3VA1163-1AA42-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-1AA42-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1163-1AA42-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-1AA42-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width101.6 mm
Depth70 mm

Product details

Part identity and key ratings

The Siemens SENTRON 3VA1163-1AA42-0JA0 is a 4-pole switch disconnector in an MCCB-style housing, rated 63 A continuous without overload or short-circuit protection — it's a pure disconnect, not a breaker. The 63 A rating holds flat across the full operating temperature range from 40 °C to 70 °C, so no derating curve to chase in a warm panel. It carries a shunt trip release (STL) for 110–127 V DC or AC 50/60 Hz, meaning the disconnect can be opened remotely via a control signal — a standard requirement for emergency-stop or safety-circuit isolation on a distribution bus. Rated operating voltage is 690 V AC and 600 V DC, with an insulation voltage of 800 V. The front face is IP40-rated.

Physical fit and panel integration

Dimensions are 101.6 mm wide, 130 mm tall, and 70 mm deep. Main circuit connections are busbar-type with front terminals. An optional motor drive is available as a field-addable extension. Mechanical service life is rated at 15,000 operating cycles.

Peer comparison: 3VA1110-5ED36-0AA0

The closest functional peer is the 3VA1110-5ED36-0AA0, a 3-pole molded case circuit breaker rated 100 A at 40 °C with thermal-magnetic overcurrent protection (TM210, LI characteristic). The 3VA1163-1AA42-0JA0 is a 4-pole switch disconnector with no overcurrent protection, so it cannot drop in as a breaker substitute. If the panel was specified around the 3VA1110-5ED36-0AA0, rewiring is required: the 3VA1163 is wider (101.6 mm vs 76.2 mm) and uses busbar connections rather than box terminals.

MPN
3VA1163-1AA42-0JA0