Skip to main content
Siemens 3VA1163-1AA42-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1163-1AA42-0KC0 Switch Disconnector, 63A

MPN3VA1163-1AA42-0KC0

Siemens SENTRON 3VA1 series switch disconnector, IEC frame 160, 4-pole SD100, 63 A, shunt trip (STL) 220-250 V DC / 208-277 V AC, 2 auxiliary switches HQ, busbar connection front terminal.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-1AA42-0KC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1163-1AA42-0KC0 — Ratings
ParameterValue
Number of poles4
Power loss, max.38 W

Construction & Connection

3VA1163-1AA42-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-1AA42-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-1AA42-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-1AA42-0KC0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1163-1AA42-0KC0 is a 4-pole switch disconnector in MCCB design, rated for 63 A continuous current (Iu) with a maximum rated operational voltage of 690 V AC (50/60 Hz) and 600 V DC. It is built on the IEC frame 160 platform and ships with a shunt trip (STL) release for 220-250 V DC or 208-277 V AC, plus two HQ auxiliary switches. The main circuit connects via busbar front terminals.

This part is a pure switch disconnector — it provides no overload or short-circuit protection. The 2 kA short-time withstand rating (1 s and 0.5 s) defines its capability to carry fault current until an upstream protective device clears it, not to interrupt a fault itself. That makes it a load-break isolator for a panel's main incoming supply or a branch feeder where protection is handled separately. The shunt trip (STL) release allows remote tripping via a control signal, useful for emergency-stop circuits or interlocking schemes. Two HQ auxiliary contacts report the main contact position back to the PLC or status lamp. No undervoltage release is fitted, so a loss of control power will not automatically open the disconnector.

Panel footprint: 130 mm height, 101.6 mm width, 70 mm depth. The front terminal arrangement accepts busbar connections for the main circuit, which simplifies panel wiring in a multi-feeder distribution assembly. Front IP40 protection means it is suitable for enclosed panel mounting where the door or cover provides the environmental seal. Operating temperature range -25 °C to +70 °C covers most indoor industrial environments; storage range -40 °C to +80 °C. Maximum power dissipation is 38 W — plan for that heat load in a sealed enclosure with restricted natural convection.

Frequently asked questions

What does the shunt trip on this disconnector require to operate?

The shunt trip (STL) release requires a control voltage of 220-250 V DC or 208-277 V AC to trip the disconnector remotely. It does not include an undervoltage release, so loss of control power will not automatically open the main contacts.

What are the key ratings for 3VA1163-1AA42-0KC0?

Rated continuous current Iu = 63 A, max rated operational voltage 690 V AC (50/60 Hz) or 600 V DC, short-time withstand 2 kA for 1 s and 0.5 s. It is a 4-pole switch disconnector with no overload or short-circuit protection.

Where can I buy 3VA1163-1AA42-0KC0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

Will 3VA1163-1AA42-0KC0 drop into a panel specified around 5SQ2670-2YA63?

No — the 5SQ2670-2YA63 is a 4-pole MCB (miniature circuit breaker) with overcurrent protection, while the 3VA1163-1AA42-0KC0 is a switch disconnector with no overcurrent protection. They serve different functions and are not drop-in interchangeable without rewiring the protection scheme.

MPN
3VA1163-1AA42-0KC0