Skip to main content
Siemens 3VA1163-3EF32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-3EF32-0AF0 SENTRON MCCB, 63 A, 3-Pole, 75.6

MPN3VA1163-3EF32-0AF0

Siemens SENTRON 3VA1163-3EF32-0AF0, molded case circuit breaker, 3-pole, 63 A rated, TM240 thermal-magnetic trip, 75.6 kA interrupting at 240 V, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-3EF32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1163-3EF32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA

Protection & Trip Unit

3VA1163-3EF32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-3EF32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-3EF32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-3EF32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-3EF32-0AF0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1163-3EF32-0AF0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with a TM240 thermal-magnetic trip unit — fixed thermal, magnetic adjustable. It's built for line protection in distribution panels, switchgear, and motor control centers where you need a compact MCCB that holds 63 A through the full 40–50 °C range and only starts derating above 55 °C (60.48 A at 55 °C, 56.7 A at 70 °C).

Interrupting capacity — what the voltages tell you

This breaker delivers 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. That's a steep drop above 440 V, so if your fault current at 690 V is anywhere near 10 kA, this unit still holds — but you're running it close to the ceiling. For most 400/415 V commercial and light industrial panels, 52.5 kA gives solid SCCR headroom without overspending on a higher-rated frame.

Panel fit and aux contacts

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without surprises. It ships with one auxiliary switch and one trip alarm switch (HQ configuration), so you get status feedback and a separate alarm contact for remote fault indication. No undervoltage release, no communication module, no ground-fault monitoring — this is a straight line-protection breaker, no extras.

Frequently asked questions

What is the interrupting capacity of this MCCB at 415 V?

52.5 kA at 415 V, which covers most 400 V distribution panels with solid headroom.

Where can I buy the 3VA1163-3EF32-0AF0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN