Skip to main content
Siemens 3VA1163-3EF32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-3EF32-0KC0 SENTRON MCCB, 63 A, 75.6 kA at 24

MPN3VA1163-3EF32-0KC0

Siemens SENTRON 3VA1163-3EF32-0KC0, molded case circuit breaker, 3-pole, 63 A, TM240 overcurrent release, 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, 10.5 kA at 690 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-3EF32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1163-3EF32-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA

Protection & Trip Unit

3VA1163-3EF32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-3EF32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-3EF32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-3EF32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-3EF32-0KC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1163-3EF32-0KC0 is a 3-pole SENTRON molded case circuit breaker rated for line protection, carrying a continuous current Iu of 63 A at 40 °C and holding that rating through 50 °C before a mild derating curve begins at 55 °C. Breaking capacity is voltage-dependent: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V — figures that govern the available fault current the breaker can safely interrupt at the point of installation.

What the ratings mean for fit

The 63 A continuous rating at 40 °C is the thermal baseline for sizing the breaker to the load. The TM240 overcurrent release provides fixed thermal-magnetic protection — no electronic adjustment, no communication, no phase-failure detection. The shunt trip (STL) auxiliary release is built in, and the breaker ships with 2 auxiliary switches HQ. The integrated auxiliary trip order code is 3VA9688-0BL33, which is the factory-matched accessory for this unit.

Panel integration and environment

Dimensions are 70 mm deep, 76.2 mm wide, and 130 mm high — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures. Front protection is IP40, meaning the operator face is protected against tools and small wires but not against water ingress; the breaker is intended for dry indoor panel environments. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

Where can I buy 3VA1163-3EF32-0KC0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1163-3EF32-0KC0 at different voltages?

Breaking capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V.

MPN