Skip to main content
Siemens 3VA1163-3EF36-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-3EF36-0AH0 SENTRON MCCB, 63 A, 3-Pole, 75.6

MPN3VA1163-3EF36-0AH0

Siemens SENTRON 3VA1 molded case circuit breaker, 3-pole, 63 A, TM240 thermal-magnetic release, 75.6 kA at 240 V, 70 mm depth, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-3EF36-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1163-3EF36-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA

Protection & Trip Unit

3VA1163-3EF36-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-3EF36-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-3EF36-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1163-3EF36-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-3EF36-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1163-3EF36-0AH0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for line protection, with a TM240 thermal-magnetic overcurrent release and a rated continuous current Iu of 63 A. Breaking capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V — covering most low-voltage distribution panels and motor branch circuits. Current rating holds at 63 A up to 50 °C ambient, then derates to 60.48 A at 55 °C and 56.7 A at 70 °C — plan your enclosure ventilation if the breaker sits near other heat sources.

Mounting and integration

Dimensions are 70 mm depth, 76.2 mm width, and 130 mm height — fits standard panel cutouts for 3VA1 frame breakers. Front face is IP40; no special sealing needed for dry indoor enclosures. Comes with 2 auxiliary switches plus 1 trip alarm switch (HQ version) for remote status feedback. No undervoltage release, no ground-fault monitoring, no communication module — this is a straight thermal-magnetic breaker for basic overcurrent protection.

MPN
3VA1163-3EF36-0AH0