Skip to main content
Siemens 3VA1163-3GF42-0AA0-ZD00 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-3GF42-0AA0-ZD00 Circuit Breaker, 63A, 25kA @

MPN3VA1163-3GF42-0AA0-ZD00

Siemens 3VA1 series, IEC frame 160, breaking capacity class N, 4-pole, In=63A, Icu=25kA @ 415V, TM240, ATAM, line protection, nut keeper kit for DC Power OEM in China.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

What it is and what it does

The Siemens 3VA1163-3GF42-0AA0-ZD00 is a 4-pole IEC frame 160 circuit breaker rated at 63 A with a breaking capacity of 25 kA at 415 V (class N). It provides line protection via a TM240 thermal-magnetic trip unit with adjustable overload protection (Ir = 44 A to 63 A) and short-circuit protection (Ii = 5 to 10 × In). The ATAM designation indicates it includes a neutral conductor protection module at 100% and a nut keeper kit, configured for DC Power OEM applications in China.

What the ratings mean for fit

The 25 kA Icu at 415 V (class N) means this breaker can safely interrupt fault currents up to that level without upstream cascading — sufficient for most industrial distribution panels where the available fault current is below that threshold. The adjustable Ir (44–63 A) lets you match the overload pickup to the actual load current, avoiding nuisance trips while still protecting the downstream cable. The Ii range of 5–10× In (315–630 A) gives flexibility for motor-start inrush or transformer magnetizing current without sacrificing short-circuit protection.

Integration and deployment context

This 4-pole breaker mounts on a standard DIN rail inside a panel enclosure. The nut keeper kit simplifies torque-controlled lug connections for DC Power OEM builds. The neutral conductor protection at 100% ensures the neutral is not overloaded in single-phase or unbalanced three-phase circuits — a common requirement in IEC distribution boards.

Frequently asked questions

Where can I buy 3VA1163-3GF42-0AA0-ZD00 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of this breaker?

The rated ultimate breaking capacity (Icu) is 25 kA at 415 V, class N per IEC 60947-2.

What does the TM240 trip unit mean?

TM240 is a thermal-magnetic trip unit with adjustable overload protection (Ir = 44 A to 63 A) and fixed short-circuit protection (Ii = 5 to 10 × In).

MPN