Siemens 3VA1163-4EF32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-4EF32-0AG0 SENTRON MCCB, 63 A, 121 kA at 240

MPN3VA1163-4EF32-0AG0

Siemens SENTRON 3VA1163-4EF32-0AG0, molded case circuit breaker, 3-pole, 63 A, TM240 thermal-magnetic release, line protection, 121 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-4EF32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB11

Ratings

3VA1163-4EF32-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1163-4EF32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-4EF32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-4EF32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-4EF32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-4EF32-0AG0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1163-4EF32-0AG0 is a SENTRON molded case circuit breaker (MCCB) for line protection, rated 63 A continuous current with a TM240 thermal-magnetic overcurrent release. It carries a 121 kA interrupting capacity at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V — so it handles high-fault utility feeds or transformer secondaries without cascading upstream breakers.

Three-pole design, 76.2 mm wide and 70 mm deep — fits a standard 3-pole MCCB slot in a SENTRON panelboard or standalone enclosure. IP40 on the front, so it's suited for indoor panel mounting where dripping water isn't a concern. The auxiliary contact version includes one auxiliary switch plus one trip alarm switch (HP type), giving a clean signal back to a PLC or annunciator on trip.

Frequently asked questions

What is the interrupting capacity of 3VA1163-4EF32-0AG0 at 415 V?

75.6 kA at 415 V, which is typical for a high-interrupting MCCB on a 400 V class distribution board.

Where can I buy 3VA1163-4EF32-0AG0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

Will 3VA1163-4EF32-0AG0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?

Both are 3-pole SENTRON MCCBs with the same 76.2 mm width and 70 mm depth, so the mechanical footprint is identical. The 3VA1163-4EF32-0AG0 is rated 63 A with a TM240 release, while the 3VA1010-2ED32-0JA0 is a lower-current variant — verify the load current and trip curve match before swapping.

MPN