Skip to main content
Siemens 3VA1163-4EF32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-4EF32-0BH0 SENTRON MCCB, 63 A, 3-Pole, 121 k

MPN3VA1163-4EF32-0BH0

Siemens SENTRON molded case circuit breaker, 3VA1163-4EF32-0BH0, 3-pole, 63 A rated at 40 °C, 121 kA breaking capacity at 240 V AC, line protection design, with undervoltage release and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-4EF32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11634EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1163-4EF32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.19.8 W

Protection & Trip Unit

3VA1163-4EF32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1163-4EF32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-4EF32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1163-4EF32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-4EF32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB carries and where it fits

The Siemens SENTRON 3VA1163-4EF32-0BH0 is a 3-pole molded case circuit breaker (MCCB) rated 63 A at 40 °C, with a breaking capacity of 121 kA at 240 V AC. That 121 kA figure at 240 V means it can safely interrupt very high fault currents in low-voltage distribution — typical for transformer-fed main feeders or large motor branch circuits where available fault current is high. The 63 A continuous rating holds steady up to 50 °C, then derates linearly to 58 A at 70 °C (–), so in a warm enclosure you still have headroom. The insulation voltage is rated 800 V, which covers 480Y/277 V and 600 V systems with margin. This is a line-protection design — meaning it is intended for cable and busbar protection, not direct motor overload protection (that would require a separate overload relay or a motor-protective breaker). It ships with an undervoltage release (UVR) fitted, so if control voltage drops, the breaker trips — a standard requirement for safety circuits that need to drop power on loss of control supply. The auxiliary switch block provides two auxiliary contacts plus one trip-alarm contact, enough to signal status and trip to a PLC or indicator lamp without an add-on module.

Dimensions and panel fit

The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep (–). That 76.2 mm width (3 inches) is the standard 3-pole MCCB footprint for this frame size — it fits the same panel cutout and DIN-rail adapter as other SENTRON 3VA1 breakers. The depth of 70 mm means it will clear a standard 200 mm deep enclosure with room for wiring and the UVR coil. Power loss is 19.8 W maximum, so thermal rise inside the panel is modest; no forced cooling needed in most layouts.

Environmental and compliance

Operating temperature range is -25 °C to 70 °C (–); storage range is -40 °C to 80 °C (–). That covers most indoor industrial environments, including unheated warehouses. The part carries a trip indicator for quick visual identification of a tripped breaker. No ground-fault monitoring version is fitted — this is a straight thermal-magnetic or electronic trip unit (line protection). Compliance documentation (RoHS, REACH, UL, IEC) is standard for the SENTRON series; the specific declarations are available on request.

Frequently asked questions

Where can I buy 3VA1163-4EF32-0BH0 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1163-4EF32-0BH0 at 240 V?

121 kA at 240 V AC. At 415 V it is 75.6 kA, at 440 V it is 52.5 kA, and at 500 V / 690 V it is 11.9 kA (–).

Will 3VA1163-4EF32-0BH0 drop into a panel specified around 3VA1110-5EF32-0AM0?

Both are 3-pole SENTRON 3VA1 breakers with the same 76.2 mm width and 130 mm height (–), so the physical footprint and DIN-rail mounting are identical. The main difference is the current rating — this one is 63 A versus the 100 A of the 3VA1110-5EF32-0AM0 — so the panel bus and cable sizing must match the lower rating. The auxiliary switch and UVR wiring positions are the same.

MPN
3VA1163-4EF32-0BH0