Siemens 3VA1163-4EF32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-4EF32-0DA0 SENTRON MCCB, 63 A, 3-Pole, 121 k

MPN3VA1163-4EF32-0DA0

Siemens SENTRON 3VA1163-4EF32-0DA0, molded case circuit breaker, 3-pole, 63 A rated continuous current Iu, TM240 overcurrent release, 121 kA interrupting at 240 V, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-4EF32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1163-4EF32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1163-4EF32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-4EF32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-4EF32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1163-4EF32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-4EF32-0DA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1163-4EF32-0DA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with a TM240 thermal-magnetic overcurrent release. It is configured for line protection — no auxiliary contacts, no communication module, no ground-fault monitoring built in. The interrupting ratings are 121 kA at 240 V and 75.6 kA at 415 V, which covers most industrial service-entrance and distribution panel fault levels. An undervoltage release (UVR) is fitted as standard; the integrated auxiliary trip uses order code 3VA9608-0BB25.

Interrupting capacity and thermal derating

The 121 kA at 240 V is the headline number for North American 240/120 V split-phase panels; the 75.6 kA at 415 V covers European 400 V three-phase distribution. At 690 V the rating drops to 11.9 kA, so this breaker is not the right choice for 690 V mains — a higher-voltage-rated frame is needed. The 63 A continuous rating holds flat from 40 °C through 50 °C; above that it derates gradually to 56.7 A at 70 °C. That means in a hot panel or enclosure with limited airflow, the actual ampacity is lower than the nameplate 63 A.

Physical fit and panel integration

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth. The 76.2 mm width matches the standard 3-pole MCCB footprint for DIN-rail or panel-mount enclosures. IP40 on the front face — suitable for enclosed distribution boards, not for washdown or outdoor exposure without an additional enclosure.

Frequently asked questions

Where can I buy 3VA1163-4EF32-0DA0 and how do I get a price?

This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for quote (RFQ) through this listing; availability and current pricing are confirmed at quote time.

What are the key interrupting ratings for 3VA1163-4EF32-0DA0?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. The 690 V rating limits its use on higher-voltage mains.

Does 3VA1163-4EF32-0DA0 include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as standard. The integrated auxiliary trip is order code 3VA9608-0BB25.

What is the thermal derating for 3VA1163-4EF32-0DA0 above 50 °C?

The 63 A rating holds through 50 °C, then derates to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.