Skip to main content
Siemens 3VA1163-5ED32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5ED32-0AB0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA1163-5ED32-0AB0

Siemens SENTRON 3VA1 series, 3-pole molded case circuit breaker, 63 A rated continuous current, TM210 thermal-magnetic release, 187 kA breaking capacity at 240 V, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1163-5ED32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA1163-5ED32-0AB0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1163-5ED32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1163-5ED32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-5ED32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1163-5ED32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-5ED32-0AB0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1163-5ED32-0AB0 is a SENTRON 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release. Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — meaning it can safely clear fault currents at those levels without upstream coordination failure.

Above that it derates linearly: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.

Auxiliary contacts and release configuration

The TM210 release is fixed thermal-magnetic — no adjustable long-time or short-time pickup. There is no communication function or phase failure detection built in. If you need those, you're looking at a different order code in the 3VA family.

Dimensions are 70 mm depth, 76.2 mm width, 130 mm height — standard 3-pole MCCB footprint for DIN-rail or screw-mount panel integration. The 2 auxiliary switches occupy the side slot; verify clearance for wiring access.

Frequently asked questions

Where can I buy 3VA1163-5ED32-0AB0 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest lead time.

What is the breaking capacity of 3VA1163-5ED32-0AB0 at different voltages?

187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — sufficient for high-fault-current industrial panels.

Does 3VA1163-5ED32-0AB0 include an undervoltage release or shunt trip?

No. This variant ships without undervoltage release, without voltage trigger (shunt trip), and without ground fault monitoring. It includes 2 auxiliary switches HP only.

What compliance documentation is available for this part?

As a Siemens SENTRON MCCB, it carries IEC 60947-2 certification. Specific RoHS, REACH, and UL documentation should be requested at quote time for your jurisdiction.

MPN
3VA1163-5ED32-0AB0