Skip to main content
Siemens 3VA1163-5EE32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EE32-0AC0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA1163-5EE32-0AC0

Siemens SENTRON 3VA1163-5EE32-0AC0, molded case circuit breaker, 3-pole, 63 A, TM220 release, 187 kA at 240 V, 2 auxiliary switches HQ, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-5EE32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1163-5EE32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1163-5EE32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220

Construction & Connection

3VA1163-5EE32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-5EE32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-5EE32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-5EE32-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

63 A MCCB with TM220 — what the ratings mean for your panel

The Siemens 3VA1163-5EE32-0AC0 is a 3-pole SENTRON molded case circuit breaker rated for 63 A continuous current at 40 °C ambient, with the same rating holding at 45 °C and 50 °C — no derating needed in a warm enclosure until you cross 55 °C, where it drops to 60.48 A. The TM220 thermal-magnetic release gives fixed thermal and magnetic trip settings; no voltage trigger or undervoltage release here, so it's a straight line-protection device for feeder or branch circuits. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — that's serious SCCR headroom for high-fault installations, especially on 240 V or 415 V distribution where you can coordinate downstream without worrying about the main.

Fit and footprint — panel integration

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without surprises. IP40 on the front means it's protected against tools and wires >1 mm, but not against moisture; keep it inside a sealed cabinet if there's washdown nearby. The 2 auxiliary switches (HQ type) are built in, so you get status feedback without adding a separate block — handy for PLC inputs or remote indication.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — these are the interrupting ratings for the 3VA1163-5EE32-0AC0.

Where can I buy 3VA1163-5EE32-0AC0 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What does the TM220 release designation mean?

TM220 is a thermal-magnetic overcurrent release — fixed thermal and magnetic trip settings, no electronic adjustment or communication function on this variant.

MPN