Skip to main content
Siemens 3VA1163-5EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EE32-0AA0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA1163-5EE32-0AA0
Active

Siemens SENTRON 3VA1163-5EE32-0AA0, molded case circuit breaker, 3-pole, 63 A, TM220 thermal-magnetic release, 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-5EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1163-5EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.17.3 W
3VA1163-5EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1163-5EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-5EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1163-5EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-5EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

63 A MCCB with TM220 release — active line, high interrupting capacity

The Siemens SENTRON 3VA1163-5EE32-0AA0 is a 3-pole molded case circuit breaker rated 63 A at 40 °C, built around a TM220 thermal-magnetic overcurrent release. The TM220 designation means the thermal element is fixed at 63 A (the frame rating) and the magnetic short-circuit pickup is adjustable from 5× to 10× In — so you set the instantaneous trip threshold between 315 A and 630 A to coordinate with downstream devices. Breaking capacity reaches 187 kA at 240 V AC, dropping to 121 kA at 415 V and 75.6 kA at 440 V, which covers most industrial service-entrance and distribution panel applications where high fault current is expected.

Above that, derating is gradual: 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C. Maximum power dissipation is 17.3 W at rated load, which matters for thermal coordination inside a sealed enclosure.

Frequently asked questions

What is the breaking capacity of 3VA1163-5EE32-0AA0 at different voltages?

At 240 V AC the breaking capacity is 187 kA; at 415 V it is 121 kA; at 440 V it is 75.6 kA; at 500 V and 690 V it is 17 kA.

What does the TM220 release mean on this MCCB?

TM220 is a thermal-magnetic release where the thermal element is fixed at the frame rating (63 A) and the magnetic short-circuit pickup is adjustable between 5× and 10× In, giving a trip range of 315 A to 630 A for coordination with downstream breakers.

Where can I buy 3VA1163-5EE32-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time.

MPN
3VA1163-5EE32-0AA0