Skip to main content
Siemens 3VA1163-5EE32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EE32-0HA0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA1163-5EE32-0HA0

Siemens SENTRON 3VA1163-5EE32-0HA0, molded case circuit breaker, 3-pole, 63 A, 187 kA at 240 V, line protection, TM220 release, shunt trip, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-5EE32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1163-5EE32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1163-5EE32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
3VA1163-5EE32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-5EE32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1163-5EE32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-5EE32-0HA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1163-5EE32-0HA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with an interrupting capacity of 187 kA at 240 V and 121 kA at 415 V — figures that hold the unit on the grid through a hard feeder fault without cascading upstream, provided the available fault current stays within those limits.

The breaker holds its full 63 A rating up to 50 °C; above that it derates linearly to 56.7 A at 70 °C, so a panel builder stacking this unit next to a transformer or drive must account for the local ambient inside the enclosure — the IP40 front means the case is protected against solid objects over 1 mm but not sealed against moisture, so keep it out of washdown zones.

The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON 3VA footprint that drops into the same panel cutout as other 3VA frame sizes, so a panel originally specified around the 3VA1110-5EE32-0JA0 will accept this unit without rewiring, provided the busbar and lug kit match the 63 A rating.

Frequently asked questions

What is 3VA1163-5EE32-0HA0's listed depth?

The depth is 70 mm.

What is 3VA1163-5EE32-0HA0's listed width?

The width is 76.2 mm.

MPN