Skip to main content
Siemens 3VA1163-5EE32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EE32-0HC0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA1163-5EE32-0HC0

Siemens SENTRON 3VA1163-5EE32-0HC0, molded case circuit breaker, 3-pole, 63 A at 40 °C, 187 kA breaking capacity at 240 V, shunt trip release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-5EE32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11635EE320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1163-5EE32-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.17.3 W

Protection & Trip Unit

3VA1163-5EE32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1163-5EE32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-5EE32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-5EE32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-5EE32-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB delivers on the line side

The Siemens SENTRON 3VA1163-5EE32-0HC0 is a 3-pole molded case circuit breaker (MCCB) rated 63 A at 40 °C, with a 187 kA interrupting capacity at 240 V AC — that SCCR covers most utility transformer secondaries and large motor branch circuits without needing a current-limiting fuse upstream. At 415 V it still interrupts 121 kA, and at 690 V it holds 17 kA, so it handles industrial 400 V distribution panels and 690 V drives as well. The thermal-magnetic trip curve is factory set for line protection (cable/feeder), not motor overload. If you need a motor-protective characteristic, this is the wrong variant — look for the 3VA1 with a different design suffix. Power loss at full load is 17.3 W — negligible for panel thermal budgeting in a standard enclosure, but worth noting if you pack multiple breakers in a sealed cabinet.

Integration and footprint

Mounts on a DIN rail or panel-mount plate. Dimensions: 130 mm height, 76.2 mm width (3 inches), 70 mm depth. The 3-pole width is standard for a 63 A frame — fits a 3-module slot on a DIN-rail assembly. Comes with two auxiliary switches (HQ type) built in — these give you two independent signal contacts for status feedback to a PLC or annunciator panel. No separate auxiliary switch block needed for basic open/closed indication. Includes a shunt trip release (STL) for remote tripping via a control signal — useful for emergency-stop circuits or remote load shedding. No undervoltage release is fitted (that would be a different order code).

Thermal derating — what the 63 A rating actually means

The 63 A rating holds steady from 40 °C up to 50 °C — no derating needed in a typical 40 °C panel. At 55 °C it drops to 62 A, at 60 °C to 61 A, and at 70 °C to 58 A. If your panel ambient runs above 50 °C, size the breaker one frame step up or accept the reduced ampacity. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. The storage limit governs handling during transport in cold climates — the breaker can sit in an unheated warehouse at -40 °C without damage.

Frequently asked questions

What does the shunt trip release do on this breaker?

The shunt trip (STL) allows remote tripping by applying a control voltage — used for emergency-stop circuits, remote load shedding, or interlocking with a fire-alarm system.

Will this breaker drop into a panel designed for 3VA1110-5EF32-0AM0?

The 3VA1163 is a larger frame (63 A vs the 3VA1110's lower rating) and has different dimensions — it will not physically interchange without rewiring and re-punching the mounting holes. The 3VA1110 is a different frame size.

MPN
3VA1163-5EE32-0HC0