The Siemens 3VA1163-5EE32-0HH0 is a 3-pole IEC frame 160 molded case circuit breaker with a 63 A thermal-magnetic trip unit (TM220). Breaking capacity class M delivers Icu=55kA at 415 V AC — enough for most industrial distribution panels where fault currents stay under that threshold. Overload protection is adjustable Ir=44A…63A via the dial; short-circuit pickup is fixed at Ii=10 x In.
For selectivity coordination downstream, the TM220 thermal-magnetic curve (fixed Ii=630 A) pairs with standard panelboard feeders. The shunt trip coil draws from a 24 V AC control transformer or a 12-30 V DC safety circuit; verify the coil's inrush doesn't drop the supply below the dropout voltage. Two HQ auxiliary switches plus one HQ trip alarm switch give status feedback for PLC inputs or remote annunciation.