Siemens 3VA1163-5EF32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EF32-0AD0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA1163-5EF32-0AD0

Siemens SENTRON 3VA1 series, molded case circuit breaker, 3VA1163-5EF32-0AD0, 3-pole, 63 A at 40 °C, TM240 thermal-magnetic release, 187 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-5EF32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11635EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1163-5EF32-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.17.3 W
3VA1163-5EF32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1163-5EF32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-5EF32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1163-5EF32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-5EF32-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1163-5EF32-0AD0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated 63 A continuous at 40 °C, with a TM240 thermal-magnetic release and a line-protection design. The interrupting rating at 240 V is 187 kA, which drops to 121 kA at 415 V and 75.6 kA at 440 V, so the SCCR headroom shrinks fast as line voltage climbs.

The 63 A rating holds flat from 40 °C through 50 °C, then tapers: 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, 58 A at 70 °C. The case dimensions are 130 mm tall, 76.2 mm wide, 70 mm deep, which is a standard 3-pole MCCB footprint for DIN-rail or screw-mount panel integration. No auxiliary switch is fitted as standard, but the basic switch variant 3VA11635EF320AA0 is the underlying platform; the -5EF32-0AD0 order code includes three HQ auxiliary switches.

Frequently asked questions

What is the interrupting capacity of this MCCB at 240 V?

187 kA at 240 V, derating to 121 kA at 415 V and 75.6 kA at 440 V.

What are the physical dimensions of 3VA1163-5EF32-0AD0?

130 mm height, 76.2 mm width, 70 mm depth — standard 3-pole MCCB footprint.

Where can I buy 3VA1163-5EF32-0AD0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does this breaker include an undervoltage release or ground-fault monitoring?

No — this variant has no undervoltage release and no ground-fault monitoring. It is a straight thermal-magnetic line-protection breaker.

MPN
3VA1163-5EF32-0AD0