Skip to main content
Siemens 3VA1163-5EF32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EF32-0BA0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA1163-5EF32-0BA0

Siemens SENTRON 3VA1163-5EF32-0BA0, molded case circuit breaker, 3-pole, 63 A rated at 40 °C, 187 kA breaking capacity at 240 V, with undervoltage release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-5EF32-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11635EF320AA0
3VA1163-5EF32-0BA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.8 W
3VA1163-5EF32-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1163-5EF32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-5EF32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1163-5EF32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-5EF32-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1163-5EF32-0BA0 is a 3-pole molded case circuit breaker rated 63 A at 40 °C, with a breaking capacity of 187 kA at 240 V. The TM240 overcurrent release handles thermal-magnetic trip characteristics.

This MCCB delivers 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. That spread covers most industrial distribution panels where high fault current is a concern at lower voltages.

Thermal derating curve

Rated current holds at 63 A from 40 °C through 50 °C, then drops to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C.

No trip indicator or voltage trigger on this variant.

Power loss and environmentals

Maximum power loss is 19.8 W — useful for thermal budget in a sealed enclosure.

Frequently asked questions

How do I get current pricing and availability for 3VA1163-5EF32-0BA0?

Submit an RFQ through this listing. Availability and pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of 3VA1163-5EF32-0BA0 at 240 V?

187 kA at 240 V, with 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V.

Does this MCCB include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as the auxiliary release type.

MPN
3VA1163-5EF32-0BA0