Skip to main content
Siemens 3VA1163-5EF32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EF32-0CA0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA1163-5EF32-0CA0

Siemens SENTRON 3VA1163-5EF32-0CA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 187 kA breaking capacity at 240 V AC, line protection version with TM240 thermal-magnetic release and undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-5EF32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1163-5EF32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1163-5EF32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1163-5EF32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-5EF32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1163-5EF32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-5EF32-0CA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — that's headroom for high-fault installations where upstream coordination matters.

Full 63 A rating holds through 50 °C ambient. At 55 °C it derates to 60.48 A, at 60 °C to 59.22 A, at 65 °C to 57.96 A, and at 70 °C to 56.7 A. That's a shallow derating curve — you don't lose much headroom in a warm enclosure.

Integrated undervoltage release — no auxiliary contacts

There are no auxiliary contacts on this version, so if you need status feedback to a PLC, plan for a separate auxiliary switch block.

Frequently asked questions

Where can I buy 3VA1163-5EF32-0CA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the breaking capacity of this MCCB at different voltages?

187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. That covers most industrial distribution voltages with substantial fault-current headroom.

Does this breaker include an undervoltage release?

Yes, it ships with an integrated undervoltage release (UVR), part number 3VA9608-0BB24 for the auxiliary trip. No auxiliary contacts are included.

What are the mounting dimensions for panel integration?

Width 76.2 mm, height 130 mm, depth 70 mm. Fits standard panel cutouts for 3-pole MCCBs in this class.

MPN
3VA1163-5EF32-0CA0