MCCB with 63 A frame and 187 kA interrupting capacity
Its TM240 thermal-magnetic trip unit holds 63 A continuously at 40 °C and derates to 58 A at 70 °C — the full curve matters when the panel ambient runs hot. The interrupting ratings climb to 187 kA at 240 V AC and stay at 121 kA at 415 V; above 500 V it still clears 17 kA, so this breaker handles high-fault utility feeds without cascading upstream. A built-in shunt trip (STL) release allows remote tripping from a PLC or emergency-stop circuit — no separate undervoltage release is fitted here.
At full 63 A load the breaker dissipates 17.3 W maximum — a factor when calculating enclosure ventilation. No trip indicator is fitted on this variant.