Skip to main content
Siemens 3VA1163-5EF32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EF32-0KA0 SENTRON MCCB, 63 A, 3-Pole, Shunt

MPN3VA1163-5EF32-0KA0

Siemens SENTRON 3VA1163-5EF32-0KA0, 3-pole molded case circuit breaker, 63 A at 40 °C, TM240 overcurrent release, shunt trip (STL), 187 kA breaking at 240 V, 70 mm depth × 76.2 mm width × 130 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-5EF32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11635EF320AA0

Ratings

3VA1163-5EF32-0KA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.17.3 W

Protection & Trip Unit

3VA1163-5EF32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1163-5EF32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-5EF32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1163-5EF32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-5EF32-0KA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

63 A MCCB with shunt trip — line protection for distribution panels

The Siemens SENTRON 3VA1163-5EF32-0KA0 is a 3-pole molded case circuit breaker rated for 63 A continuous at 40 °C, with a TM240 thermal-magnetic overcurrent release and an integrated shunt trip (STL) for remote tripping. It's designed for line protection in main distribution boards and sub-distribution panels, where the 187 kA breaking capacity at 240 V handles high-fault scenarios without cascading upstream. The 76.2 mm width (3 in) and 70 mm depth (2.76 in) fit standard SENTRON panel footprints — no rework needed for a drop-in replacement in an existing 3VA1 lineup.

Breaking capacity across voltage levels

This MCCB delivers 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. The steep drop above 440 V means you need to verify the available fault current at the installation point — at 690 V the 17 kA rating still covers most industrial secondary distribution, but not primary feeds. The TM240 release is fixed, so no field adjustment of the thermal or magnetic trip settings.

Sourcing and availability

The 3VA1163-5EF32-0KA0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. For BOM freeze or line-down situations, the active lifecycle means no last-time-buy pressure — but always confirm lead time at quote, as industrial MCCB demand can tighten supply windows.

Frequently asked questions

Where can I buy 3VA1163-5EF32-0KA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at 240 V?

187 kA at 240 V, which covers high-fault industrial distribution panels without cascading upstream breakers.

What is the width of 3VA1163-5EF32-0KA0?

76.2 mm (3 in), matching the standard SENTRON 3-pole MCCB footprint for drop-in replacement.

Does this breaker include a shunt trip?

Yes, it has a shunt trip (STL) auxiliary release for remote tripping, part of the 3VA1 design.

MPN
3VA1163-5EF32-0KA0