Skip to main content
Siemens 3VA1163-5EF36-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EF36-0BH0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA1163-5EF36-0BH0

Siemens SENTRON 3VA1163-5EF36-0BH0, 3-pole molded case circuit breaker, 63 A rated continuous current, 187 kA interrupting at 240 V, TM240 overcurrent release, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-5EF36-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1163-5EF36-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1163-5EF36-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1163-5EF36-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-5EF36-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1163-5EF36-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-5EF36-0BH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The interrupting ratings climb to 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V, giving it serious fault-clearing headroom for high-available-fault-current panels.

Above that it derates linearly: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.

Auxiliary and undervoltage release

This variant ships with two auxiliary switches plus one trip-alarm switch (HQ configuration). The integrated auxiliary trip module carries order code 3VA9608-0BB11. No communication function or phase-failure detection is fitted.

Panel fit and protection class

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint for DIN-rail or screw-mount panel integration.

Frequently asked questions

What is the interrupting rating of 3VA1163-5EF36-0BH0 at 415 V?

At 415 V the interrupting rating is 121 kA. At 240 V it is 187 kA, at 440 V it is 75.6 kA, and at 690 V it is 17 kA.

What overcurrent release does this MCCB use?

It uses a TM240 thermal-magnetic release — a fixed thermal element paired with a magnetic trip set to open instantaneously at 240 A.

Where can I buy 3VA1163-5EF36-0BH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does 3VA1163-5EF36-0BH0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) that trips the breaker when supply voltage drops below the release threshold.

MPN
3VA1163-5EF36-0BH0