Skip to main content
Siemens 3VA1163-5EF36-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EF36-0CA0 SENTRON MCCB, 63 A, 3-Pole, Line

MPN3VA1163-5EF36-0CA0

Siemens SENTRON 3VA1163-5EF36-0CA0, molded case circuit breaker, 3-pole, 63 A, line protection, TM240 overcurrent release, undervoltage release, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-5EF36-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1163-5EF36-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1163-5EF36-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-5EF36-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-5EF36-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1163-5EF36-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-5EF36-0CA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB is and where it fits

The Siemens SENTRON 3VA1163-5EF36-0CA0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current, configured for line protection — meaning it protects cables and busbars from overload and short-circuit, not motor loads. The TM240 overcurrent release gives a fixed thermal-magnetic trip curve. It carries an undervoltage release (UVR) that drops the breaker when control voltage falls below a threshold, which is useful for emergency-stop circuits or undervoltage protection on a panel feed. Breaking capacity hits 187 kA at 240 V and 121 kA at 415 V, so it handles high-fault-current points like main distribution boards or transformer secondaries.

Ratings that decide fit

The 63 A rating holds flat from 40 °C to 50 °C, then begins to derate: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. If your panel ambient runs above 50 °C, the effective continuous current drops — size the breaker for the derated value, not the nameplate 63 A. The 800 V rated insulation voltage (Ui) means it can be used on 480 V or 600 V systems without de-rating for voltage. The front face is IP40, so the breaker is protected against tools and small wires but not against water spray — keep it inside a sealed enclosure if washdown is present.

Panel integration notes

The breaker measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or screw-mount panel layouts. No auxiliary contact is included; if you need a status feedback signal, order the auxiliary contact block separately. The undervoltage release is wired to a separate control circuit; verify the coil voltage matches your control supply before energizing.

Frequently asked questions

Where can I buy 3VA1163-5EF36-0CA0 and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at 415 V?

It is rated for 121 kA at 415 V, which covers most industrial main-feeder fault levels.

Does this breaker include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as standard, part of the auxiliary release design.

What is the continuous current rating at 55 °C?

At 55 °C the continuous current derates to 60.48 A; at 60 °C it is 59.22 A, and at 70 °C it is 56.7 A.

MPN