Skip to main content
Siemens 3VA1163-5EF36-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EF36-0DC0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA1163-5EF36-0DC0

Siemens SENTRON 3VA1 molded case circuit breaker, 3VA1163-5EF36-0DC0, 63 A, 3-pole, line protection, 187 kA breaking capacity at 240 V AC, with undervoltage release and 2 HQ auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-5EF36-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11635EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1163-5EF36-0DC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.19.8 W

Protection & Trip Unit

3VA1163-5EF36-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1163-5EF36-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-5EF36-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-5EF36-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-5EF36-0DC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1163-5EF36-0DC0 — SENTRON MCCB, 63 A, 3-Pole, Line Protection

The Siemens 3VA1163-5EF36-0DC0 is a SENTRON-series molded case circuit breaker (MCCB) rated for 63 A continuous current at 40 °C, with a 3-pole construction designed for line protection. Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, and 75.6 kA at 440 V — figures that cover high-fault utility feeds and large motor branch circuits without needing a current-limiting fuse upstream. The unit ships with an integrated undervoltage release (UVR) and two HQ auxiliary switches, so it arrives ready for remote trip indication and undervoltage protection in a single package.

Ratings and What They Mean for Fit

The 63 A rating holds across 40 °C to 50 °C ambient without derating; at 70 °C it still carries 58 A. That thermal curve matters when the breaker sits in a crowded panel — you can load it to nameplate at typical enclosure temperatures without oversizing. The 187 kA at 240 V is a high-interrupting rating for a 63 A frame, meaning this breaker can be applied on the secondary of a large transformer or at a service entrance where available fault current is substantial, without needing a series-rated combination. The 800 V rated insulation voltage (Ui) confirms the breaker is suitable for 480 V and 600 V class systems with margin; the 17 kA rating at 690 V extends its use into 690 V industrial networks common in mining and marine installations.

Built-In Auxiliaries and Release

This variant includes an undervoltage release (UVR) and two HQ auxiliary switches as standard — no separate order or field-fit kit needed. The UVR drops the breaker on loss of control voltage, which is a typical requirement for safety circuits and emergency-stop chains. The two auxiliary switches provide status feedback (open/closed) to a PLC or indication lamp, saving a DIN-rail terminal block and a wiring step.

Physical Fit and Panel Integration

The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep — a 3-pole frame that fits standard Siemens 3VA1 panel cutouts and busbar systems. The 76.2 mm width is three 25.4 mm pole pitches, matching the common 25 mm modular grid for DIN-rail or direct-mount enclosures. Depth of 70 mm leaves room behind the panel for wiring and busbar connections without forcing a deeper enclosure.

Power Loss and Thermal Management

Maximum power dissipation is 19.8 W at rated load. In a sealed enclosure with multiple breakers, that heat adds up — plan for ventilation or derating if the panel ambient exceeds 50 °C. The operating temperature range of -25 °C to 70 °C covers most indoor industrial environments.

Frequently asked questions

How do I get current pricing and availability for 3VA1163-5EF36-0DC0?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1163-5EF36-0DC0 at different voltages?

The breaker is rated for 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V.

Does 3VA1163-5EF36-0DC0 include an undervoltage release?

Yes, this variant is equipped with an undervoltage release (UVR) as standard, along with two HQ auxiliary switches.

MPN
3VA1163-5EF36-0DC0