Skip to main content
Siemens 3VA1163-5EF46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5EF46-0AA0 SENTRON MCCB, 63 A, 4-Pole, 187 k

MPN3VA1163-5EF46-0AA0
Active

Siemens SENTRON 3VA1163-5EF46-0AA0, molded case circuit breaker, 4-pole, 63 A at 40 °C, TM240 overcurrent release, breaking capacity 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1163-5EF46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1163-5EF46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.17.3 W
3VA1163-5EF46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1163-5EF46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-5EF46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1163-5EF46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-5EF46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The 3VA1163-5EF46-0AA0 is a Siemens SENTRON 4-pole molded case circuit breaker rated 63 A continuous at 40 °C, with the TM240 thermal-magnetic release handling overload and short-circuit protection for line protection duty. At 440 V it's rated 75.6 kA, and at 500 V or 690 V it drops to 17 kA — still respectable for most motor control center applications, but you'll want to verify the available fault current at the point of installation. The 63 A rating holds steady up to 50 °C; above that it derates smoothly to 58 A at 70 °C, which the spec table lays out in 5 °C steps.

This MCCB measures 70 mm deep by 101.6 mm wide by 130 mm tall — a compact footprint that fits standard panel-mount cutouts for 4-pole breakers in this class.

Frequently asked questions

How do I get current pricing and availability for 3VA1163-5EF46-0AA0?

Pricing and stock levels are confirmed at quote time. Submit an RFQ through our sourcing desk and we'll return current availability and a firm price for your quantity.

What is the breaking capacity of this MCCB at 415 V?

At 415 V AC the 3VA1163-5EF46-0AA0 is rated for 121 kA breaking capacity, which covers most industrial distribution panels with high fault current.

What overcurrent release does this breaker use?

It uses a TM240 thermal-magnetic release — a fixed thermal trip curve combined with a magnetic short-circuit pickup, designed for line protection duty in the SENTRON 3VA series.

MPN