The Siemens 3VA1163-5MH32-0AD0 is a 3-pole IEC molded-case circuit breaker from the 3VA1 series, built on the 160 A frame with breaking capacity class M. Its interrupting rating is 55 kA at 415 V AC — that is the Icu (ultimate breaking capacity) per IEC 60947-2, meaning it can safely clear a fault up to that level once without damage to the breaker. Rated at 63 A (In) and fitted with a TM120M trip unit, this breaker is configured for starter protection — the TM120M provides thermal-magnetic overload and short-circuit protection, with an adjustable short-circuit pickup (Ii) from 5 to 15 times In. Note the description states 'without overload protection short-circuit protection' which indicates the TM120M is set for magnetic-only short-circuit protection; the overload function is not active, so upstream or separate overload relay must handle thermal protection for the motor. The breaker ships with a nut keeper kit and three HQ auxiliary switches (form C contacts) for remote status indication. Mounts on a standard DIN rail or panel-mount base inside the enclosure.

Siemens 3VA1163-5MH32-0AD0 Circuit Breaker, 63A, 55kA @ 415V
MPN3VA1163-5MH32-0AD0
Siemens 3VA1 series, IEC frame 160, breaking capacity class M, 3-pole, 63A, Icu=55kA @ 415V, starter protection TM120M, nut keeper kit, 3 auxiliary switches HQ.
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026
Product details
Frequently asked questions
What are the key ratings of the 3VA1163-5MH32-0AD0?
It is a 3-pole IEC frame 160 MCCB rated 63 A with a breaking capacity of 55 kA at 415 V AC (Icu). The TM120M trip unit provides adjustable short-circuit protection from 5 to 15 times In, but overload protection is not active on this variant.
MPN