Rated at In=63 A with a TM120M thermal-magnetic trip unit, this breaker provides starter protection (motor circuit) via an adjustable magnetic short-circuit release set at Ii=5…15 × In. Note the absence of integral overload protection — the TM120M here is configured for short-circuit protection only, meaning a separate motor overload relay must be wired upstream or in the starter assembly.
Accessories and control wiring