Skip to main content
Siemens 3VA1163-5MH36-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-5MH36-0KH0 Circuit Breaker, 55kA @ 415V, 63A

MPN3VA1163-5MH36-0KH0

Siemens 3VA1 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 3-pole, starter protection TM120M, In=63A, short-circuit protection Ii=5...15 x In, clamp connection, shunt trip (STL) 220-250 V DC; 208-277 V AC, 2 auxiliary switches HQ, 1 trip alarm switch HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

What this breaker does

The 3VA1163-5MH36-0KH0 is a 3-pole IEC molded-case circuit breaker on a 160 A frame, rated 63 A continuous with a TM120M thermal-magnetic trip unit. The 'M' breaking capacity class delivers 55 kA interrupting capacity at 415 V AC — enough to handle high-fault utility feeds or large motor branch circuits without cascading upstream. The trip is set for starter protection (motor short-circuit only; no overload — that's handled by the external overload relay). Short-circuit pickup Ii is adjustable 5 to 15 x In, so you tune it to the motor's locked-rotor current. A built-in shunt trip (STL) accepts 220-250 V DC or 208-277 V AC for remote emergency-off or PLC-driven trip. Two auxiliary switches (HQ) and one trip alarm switch (HQ) report breaker status and fault condition back to the control system. Clamp-type terminals accept copper or aluminum conductors without lug kits — speeds panel wiring.

MPN
3VA1163-5MH36-0KH0