Siemens 3VA1163-6EF32-0DA0 SENTRON MCCB, 63 A, 220 kA at 240

MPN3VA1163-6EF32-0DA0

Siemens SENTRON 3VA1163-6EF32-0DA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, TM240 overcurrent release, 220 kA interrupting at 240 V, undervoltage release included, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-6EF32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1163-6EF32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1163-6EF32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-6EF32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-6EF32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1163-6EF32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-6EF32-0DA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

63 A MCCB with 220 kA interrupting — line protection focus

The Siemens 3VA1163-6EF32-0DA0 is a SENTRON molded case circuit breaker rated for 63 A continuous current (Iu) across the ambient range up to 50 °C, with derating starting at 55 °C to 60.48 A and dropping to 56.7 A at 70 °C. The interrupting ratings are 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V — these are the fault-clearing capacities the breaker can safely interrupt without upstream damage. The TM240 thermal-magnetic release handles overload and short-circuit protection. An undervoltage release is built in, so if control voltage drops, the breaker trips; the auxiliary trip accessory (3VA9608-0BB25) is ordered separately.

Panel fit and integration constraints

The 3-pole breaker occupies 76.2 mm width, 130 mm height, and 70 mm depth. IP40 on the front means it's protected against tools and small wires entering from the panel face but not sealed against moisture — mount in a dry enclosure. No auxiliary contacts are integrated, so if you need status feedback, plan for the separate 3VA9608-0BB25 auxiliary trip module. The undervoltage release is wired to a separate control circuit; verify coil voltage compatibility with your 24 VDC or 110 VAC supply before termination.

What the ratings mean for selectivity

The 220 kA SCCR at 240 V and 154 kA at 415 V put this breaker in the high-interrupting category — suited for transformer secondaries or large busway feeds where available fault current exceeds 100 kA. The TM240 release provides fixed thermal pickup and magnetic trip; adjustability is limited, so coordination studies should verify the trip curve against downstream breakers. The 800 V rated insulation voltage (Ui) covers most 480 V and 600 V class systems with margin.

Frequently asked questions

Where can I buy 3VA1163-6EF32-0DA0 and how is it quoted?

This part is sourced and quoted to order through independent distribution channels. Availability and current pricing are confirmed at quote time against an RFQ — no stock count or price is published here.

What is the closest functional second-source to 3VA1163-6EF32-0DA0?

No direct functional second-source exists within the SENTRON family. The 3VA1010-2ED32-0JA0 is a different frame size and rating — it will not drop into a panel wired for this breaker without rewiring and coordination review.

What are the key specs: depth, width, and interrupting ratings?

Depth is 70 mm, width is 76.2 mm, height is 130 mm. Interrupting capacity is 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V.

MPN