Specifications

3VA1163-6EF32-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1163-6EF32-0DH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA
3VA1163-6EF32-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1163-6EF32-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1163-6EF32-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1163-6EF32-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1163-6EF32-0DH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Its breaking capacity scales with system voltage: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V. The thermal derating is minimal up to 50 °C (full 63 A), then drops to 60.48 A at 55 °C and 56.7 A at 70 °C, so a panel ambient above 50 °C requires a de-rate check against the connected load. This means the breaker can signal its status and trip condition back to a PLC or control system without an add-on module.

Integration and deployment context

Dimensions are 130 mm height, 76.2 mm width, and 70 mm depth — a standard 3-pole MCCB footprint that fits most SENTRON panelboards. The latching endurance is rated at 15,000 cycles, which governs mechanical life in frequent-switching applications.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

At 415 V, the breaking capacity is 154 kA. This is the maximum fault current the breaker can safely interrupt at that voltage level.

What auxiliary contacts come with the 3VA1163-6EF32-0DH0?

It includes 2 auxiliary switches plus 1 trip alarm switch HQ, allowing status and trip signaling back to a control system.

Where can I buy the 3VA1163-6EF32-0DH0?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
3VA1163-6EF32-0DH0