Skip to main content
Siemens 3VA1163-6EF36-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-6EF36-0BC0 SENTRON MCCB, 63A TM240, 220kA @2

MPN3VA1163-6EF36-0BC0

Siemens SENTRON 3VA1, molded case circuit breaker, line protection, 3-pole, 63 A, TM240 thermal-magnetic release, 220 kA at 240 VAC, with undervoltage release and 2 HQ auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-6EF36-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1163-6EF36-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1163-6EF36-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-6EF36-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-6EF36-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1163-6EF36-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-6EF36-0BC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

63 A MCCB with TM240 release — 220 kA SCCR at 240 V

The Siemens 3VA1163-6EF36-0BC0 is a SENTRON 3VA1 molded case circuit breaker rated for 63 A continuous current with a TM240 thermal-magnetic trip unit. Its interrupting capacity hits 220 kA at 240 VAC, 154 kA at 415 VAC, and 121 kA at 440 VAC — numbers that put it in the high-fault tier for industrial distribution panels where upstream transformer capacity is substantial. The TM240 release provides thermal overload and magnetic short-circuit protection for line protection. Rated insulation voltage is 800 V.

Built-in undervoltage release and auxiliary switches

This variant ships with an integrated undervoltage release (UVR) and two HQ auxiliary switches — the auxiliary trip module is order code 3VA9608-0BB11. The UVR drops the breaker on loss of control voltage, which is standard for safety disconnects and emergency-off circuits where you want the breaker to latch out after a voltage dip. No communication module, no ground-fault monitoring, no phase-failure detection on this build — it's a straight line-protection breaker with hardwired aux contacts. Trip indicator is not fitted; status comes from the aux switches.

Thermal derating and panel fit

Rated 63 A from 40 °C through 50 °C ambient; derating begins at 55 °C (60.48 A) and drops to 56.7 A at 70 °C. That's a clean thermal curve — no surprise drop at 45 °C. Storage range is -40 °C to 80 °C; operating range -25 °C to 70 °C. Three-pole, 76.2 mm wide, 130 mm tall, 70 mm deep — fits standard MCCB panel cutouts. Front protection is IP40, so it's fine for enclosed switchboards but not washdown areas.

Frequently asked questions

What auxiliary options come on this breaker?

It includes an undervoltage release and two HQ auxiliary switches; the auxiliary trip module is order code 3VA9608-0BB11.

MPN
3VA1163-6EF36-0BC0