Siemens 3VA1163-6EF36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-6EF36-0JA0 SENTRON MCCB, 63 A, 220 kA at 240

MPN3VA1163-6EF36-0JA0

Siemens SENTRON 3VA1163-6EF36-0JA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, TM240 thermal-magnetic release, 220 kA at 240 V, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-6EF36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1163-6EF36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1163-6EF36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1163-6EF36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-6EF36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1163-6EF36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-6EF36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1163-6EF36-0JA0 — 63 A MCCB for high-fault panels

The Siemens 3VA1163-6EF36-0JA0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current in a 3-pole line protection configuration. Its TM240 thermal-magnetic release provides overload and short-circuit protection without electronic adjustments — a fixed-trip design that eliminates setting drift over temperature. The breaker carries a 220 kA interrupting rating at 240 V, dropping to 154 kA at 415 V and 121 kA at 440 V, which puts it in the high-breaking-capacity class for main feeders or large secondary distribution where fault currents are severe.

What the ratings mean for your panel

The 63 A rating holds across ambient temperatures up to 50 °C (–); above that it derates linearly to 56.7 A at 70 °C. That thermal profile matters for enclosures with poor airflow — if the panel ambient runs at 55 °C, the breaker's usable current drops to 60.48 A, so the load must be sized accordingly. The 220 kA at 240 V is the SCCR (short-circuit current rating) the breaker can safely interrupt without welding contacts or venting arc gas — critical for coordination studies on 480 V / 277 V services where the available fault current can exceed 100 kA. Rated insulation voltage is 800 V, so the breaker can be applied on 690 V systems (where its breaking capacity is 17 kA,) without derating the insulation.

Panel fit and wiring

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep. The 76.2 mm width is a standard 3-pole MCCB footprint — it occupies three 25.4 mm module positions on a DIN rail, so a panel designed for a typical 63 A frame will accept this without re-drilling the mounting plate. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. Mechanical endurance is rated at 15,000 operations. Reference code per DIN EN 81346-2 is Q.

Frequently asked questions

Where can I buy 3VA1163-6EF36-0JA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1163-6EF36-0JA0 at different voltages?

220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V (–). The high 240 V rating suits it for main breakers on low-voltage services where fault current exceeds 100 kA.

Does 3VA1163-6EF36-0JA0 have a shunt trip or auxiliary contacts?

It includes a factory-fitted shunt trip release (STL, subassembly 3VA9688-0BL32) for remote tripping, but no auxiliary contacts, undervoltage release, or communication module.

What is the ambient temperature derating for this MCCB?

Rated 63 A up to 50 °C; derates to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C (–). Panel designers must account for this in tight enclosures.

MPN