It carries a continuous current of 63 A at 40 °C, with minimal thermal derating: 63 A holds through 50 °C, then steps down to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C. The interrupting capacity reaches 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V.
The 3-pole design fits typical 3-phase distribution sub-feeders. Power loss is 17.3 W maximum, which should be factored into enclosure thermal calculations.
It does not carry an undervoltage release, ground-fault monitoring, or communication function. The trip indicator is not fitted. The supplied basic switch order code is 3VA11636EF360AA0.