Skip to main content
Siemens 3VA1163-6EF36-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-6EF36-0JH0 SENTRON MCCB, 63 A, 220 kA

MPN3VA1163-6EF36-0JH0

Siemens SENTRON 3VA1 molded case circuit breaker, 3VA1163-6EF36-0JH0, 3-pole, 63 A, 220 kA breaking capacity at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1163-6EF36-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11636EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1163-6EF36-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.17.3 W

Protection & Trip Unit

3VA1163-6EF36-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1163-6EF36-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1163-6EF36-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1163-6EF36-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1163-6EF36-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB is and what it does

The Siemens 3VA1163-6EF36-0JH0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection in distribution panels. Rated 63 A continuously at 40 °C with an insulation voltage of 800 V, it handles fault interruption up to 220 kA at 240 V — that rating means it can safely clear high-fault-current events without upstream damage, critical for industrial switchboards where available fault current is high. The 3-pole construction suits three-phase feeders, and the integrated shunt trip (STL) release allows remote tripping from a safety circuit or emergency-stop chain.

Breaking capacity and thermal derating

Breaking capacity drops with system voltage: 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V or 690 V. For a 480 V panel, the 121 kA figure still leaves generous headroom above typical 65 kA SCCR requirements. The thermal rating holds at 63 A from 40 °C through 50 °C (–), then derates to 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C — a gentle slope that keeps the breaker usable in warm enclosures without oversizing the frame.

Panel fit and integration

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth. The 3-pole frame mounts in standard distribution panel cutouts; the 70 mm depth fits shallow enclosures where deeper MCCBs would conflict with wiring ducts or door-mounted devices. The trip indicator and voltage trigger are present — the trip flag gives a visual cue during fault finding without opening the cover.

MPN
3VA1163-6EF36-0JH0