Skip to main content
Siemens 3VA1163-6MH32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-6MH32-0AG0 Circuit Breaker, 70kA @ 415V, 63A

MPN3VA1163-6MH32-0AG0

Siemens 3VA1 IEC frame 160, breaking capacity class H, 70kA @ 415V, 3-pole, starter protection TM120M, 63A, short-circuit protection Ii=5...15 x In, with nut keeper kit, 1 auxiliary switch HP, 1 trip alarm switch HP.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

The Siemens 3VA1163-6MH32-0AG0 is a 3-pole IEC frame 160 circuit breaker from the 3VA1 series, rated for 63 A with a breaking capacity class H delivering 70 kA at 415 V. It is configured as a starter protection device using a TM120M thermal-magnetic release, but without integrated overload protection — it provides short-circuit protection only, with an adjustable instantaneous trip setting (Ii) from 5 to 15 times In. The unit includes a nut keeper kit, one auxiliary switch (HP), and one trip alarm switch (HP).

What the ratings mean for fit

The 70 kA Icu at 415 V places this in the high-breaking-capacity class (class H) for the 3VA1 frame, meaning it can safely interrupt fault currents up to that level without upstream cascading — critical for panels with high available fault current. The TM120M release is a thermal-magnetic type; because overload protection is omitted, this breaker is intended solely for short-circuit backup in a motor starter combination where a separate overload relay handles the thermal protection. The adjustable Ii of 5–15 x In (315–945 A instantaneous pickup) lets you coordinate with downstream contactors and relays. The nut keeper kit secures the breaker on the DIN rail or mounting plate — standard for 3VA1 frames. The auxiliary switch and trip alarm switch provide remote status feedback (open/closed and tripped), which is typical for PLC or SCADA integration in motor control centers.

Frequently asked questions

How do I get current pricing and availability for 3VA1163-6MH32-0AG0?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution channels.

What does the 70 kA breaking capacity at 415 V mean for my panel?

It means the breaker can safely interrupt fault currents up to 70 kA at 415 V without failing, which is essential for panels with high available fault current — typical in industrial MCCs. This is the class H rating for the 3VA1 frame.

MPN
3VA1163-6MH32-0AG0