Skip to main content
Siemens 3VA1163-6MH32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1163-6MH32-0JC0 Circuit Breaker, 70kA @ 415V

MPN3VA1163-6MH32-0JC0

Siemens 3VA1 series, IEC frame 160, breaking capacity class H, 3-pole, 70kA Icu @ 415V, In=63A, starter protection TM120M, with shunt trip STL 110-127V AC/DC, 2 auxiliary switches HQ, nut keeper kit.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

The Siemens 3VA1163-6MH32-0JC0 is a 3-pole IEC molded case circuit breaker in the 3VA1 series, on a 160 A frame but fitted with a 63 A TM120M thermal-magnetic trip unit configured for starter protection — meaning it is sized for motor branch-circuit short-circuit protection without built-in overload protection, which is handled separately by an external overload relay. The 'H' breaking capacity class delivers 70 kA Icu at 415 V, so it can safely interrupt fault currents up to that level without upstream cascading — a key spec for high-fault panels where the available short-circuit current is known to be above 25 kA.

This breaker includes a shunt trip (STL) rated 110-127 V AC/DC and two HQ auxiliary switches for remote status feedback. The nut keeper kit is pre-installed, which simplifies panel mounting on a DIN rail or mounting plate — one less loose part to track during assembly. The magnetic short-circuit pickup Ii is adjustable from 5 to 15 times In (315 A to 945 A), giving flexibility to ride through motor inrush without nuisance tripping.

Frequently asked questions

Where can I buy 3VA1163-6MH32-0JC0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of this circuit breaker?

It has a breaking capacity class H with Icu = 70 kA at 415 V, meaning it can safely interrupt fault currents up to 70,000 A at that voltage without damage.

Does this breaker include overload protection?

No — the TM120M trip unit is configured for starter protection, providing only short-circuit and magnetic protection. Overload protection must be provided by a separate external overload relay in the motor starter circuit.

MPN
3VA1163-6MH32-0JC0