The Siemens 3VA1163-6MH36-0AH0 is a 3-pole molded-case circuit breaker from the 3VA1 IEC frame 160 series, rated 63 A continuous current with a breaking capacity class H — Icu of 70 kA at 415 V AC. The TM120M thermal-magnetic trip unit is configured for starter protection: the thermal element is sized for motor inrush, and the magnetic instantaneous pickup is adjustable from 5 to 15 times In (315 to 945 A), letting you dial it in for the locked-rotor current of the load. This variant ships without overload protection (the TM120M provides only short-circuit and ground-fault protection), so it relies on a separate overload relay upstream or at the motor.

Siemens 3VA1163-6MH36-0AH0 Circuit Breaker, 63A, 70kA @ 415V
Siemens 3VA1 series, IEC frame 160, breaking capacity class H, Icu=70kA @ 415V, 3-pole, starter protection TM120M, AM, In=63A, without overload protection, short-circuit protection Ii=5...15 x In, clamp connection, 2 auxiliary switches HQ, 1 trip alarm switch HQ.
Product details
Frequently asked questions
Where can I buy 3VA1163-6MH36-0AH0 and how do I get a price?
This part is sourced to order against an RFQ. Submit a request through the storefront; availability and current pricing are confirmed at quote time.
What is the breaking capacity of this MCCB?
The breaking capacity class H gives an Icu of 70 kA at 415 V AC. That is the maximum fault current the breaker can interrupt without damage.
Does this breaker include overload protection?
No. The TM120M trip unit provides short-circuit and ground-fault protection only. A separate overload relay is required for motor overload protection.